TM 10-4110-262-13&P
DIRECT SUPPORT MAINTENANCE
ADVANCED DESIGN REFRIGERATOR, 300 CUBIC FOOT (ADR-300)
REFRIGERATION UNIT COMPRESSOR
REMOVE/INSTALL
INITIAL SETUP
References
Tools and special tools
None
Tool Kit, Refrigeration Service
Equipment Conditions
ADR-300 shut down and disconnected from all
Materials and Parts
power sources.
Rags (WP 0068 00, Item 15)
Personnel Required
HVAC Technician (MOS 52C, AFSC 3E1x1) (2)
NOTE
The following procedures involve servicing the refrigeration system.
Some of these service procedures are regulated by Federal, and in some
cases, by State and Local laws. All regulated refrigeration service
procedures must be performed by an EPA certified technician, using
approved equipment and complying with all Federal, State, and Local
laws.
NOTE
It is generally good practice to replace the filter dehydrator whenever the
high side is opened or when the low side is opened for an extended
period of time.
NOTE
Keep the compressor ports and open refrigerant lines covered to prevent
contaminating the system components.
REMOVE
1. Remove the condenser top and front grilles and the bottom panel from the refrigeration unit.
2. Recover the refrigerant charge from the system.
3. Disconnect the discharge and suction hoses.
0033 00-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |