![]() TM 10-4110-262-13&P
0033 00
4. Open the electrical box on top of the compressor. Tag the wires and disconnect all wires to the
compressor and remove them from the box.
5. Remove the condenser support bracket.
6. Remove the suction line insulation.
7. Remove the LPCO switch.
a. Locate the low pressure cut-out switch near the receiver on the suction line (see figure). Cut any
wire ties restraining the switch wires.
b. Disconnect the weather-tight connector on the LPCO.
CAUTION
Use a backup wrench on the low pressure switch and the schrader valve.
Lines could break causing a leak. Failure to comply may result in
damage to equipment.
c.
Unscrew the switch and remove it from the schrader valve.
8. Remove the core of the LPCO switch schrader valve.
9. Wrap the suction pressure regulator with a wet cloth.
10. Unsolder the suction pressure regulator at the elbow just above the schrader valve.
11. Unbolt the suction line from the compressor.
12. Remove the suction pressure regulator.
13. Remove the HPCO switch.
a. Disconnect the wires from the switch.
b.
Remove the HPCO switch using a backup wrench.
14. Unbolt the discharge service valve.
15. Unsolder the high pressure line just to the left of the HPCO switch port.
16. Gently bend the discharge lines to clear the compressor.
17. Remove the four compressor mounting nuts and mounting spacers.
18. Remove the compressor by lifting the unit straight up.
0033 00-2
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |