TM 10-4110-262-13&P
0034 00
WARNING
Evaporator and condenser coil fins are sharp and can severely cut hands
and other exposed body parts on contact. Take care to avoid contacting
coil fins. Failure to comply may result in serious injury to personnel.
CAUTION
Be careful to avoid bending or damaging evaporator and condenser coil
fins. Damaged fins will reduce ADR-300 performance. Protect fins with
a rigid cover while working on or near either coil. Failure to comply may
result in damage to equipment.
REMOVE
1. Recover the refrigerant charge.
2. Remove the condenser or evaporator cover as appropriate.
CAUTION
Take care to protect surrounding components from heat during soldering
and unsoldering.
3. Locate the tubing section to be replaced and the closest solder joints in both directions along the
tube.
4. Unsolder both joints and remove the tube section.
INSTALL
CAUTION
Do not contaminate the system when preparing refrigeration tubing for
soldering. Contamination may cause restrictions in the refrigeration
system. Failure to comply may result in damage to the equipment.
1. Clean the mating surfaces of the tubes for soldering.
2. Assemble the tube components in the location in which they will be soldered.
3. Solder the connections taking care to protect nearby components from heat.
4. Perform a system cleanup as described below:
0034 00-2
|