0034 00
a. Recover the refrigerant.
b. Remove the suction pressure regulator and install a temporary suction line cleanup filter.
c.
Change the compressor oil as described in WP 0031 00.
d. Change the expansion valve nozzle.
e. Change the dehydrator as described in WP 0037 00.
f.
Leak check, evacuate, and charge the system.
g. Run the unit for at least six hours.
h. Acid test the oil.
i.
If the acid test fails, change the dehydrator, and begin process starting from Step c.
j.
If the acid test passes, perform low side pump down (WP 0031 00).
k.
Remove the suction line cleanup filter.
l.
Reinstall the suction pressure regulator.
m. Leak check, evacuate, and open all valves.
n. Perform a system check.
5. Replace the dehydrator.
6. Pressurize the system with dry nitrogen and test for leaks.
7. Evacuate the system and recharge as described in WP 0031 00.
8. Reinstall the cover.