TM 10-8145-222-23
0016
SERVICE CONTINUED
3. Shut refrigeration unit down (TM 10-8145-222-10, Operating Procedures).
4. Frontseat (close) discharge (Figure 2, Item 2) service valve and slowly bleed remaining refrigerant from
compressor.
5. Remove oil drain plug (Figure 2, Item 4) from compressor.
6. Drain required amount of oil from compressor and discard in accordance with unit SOP.
7. Install oil drain plug (Figure 2, Item 4) in compressor and tighten.
8. Open discharge (Figure 2, Item 2) and suction (Figure 2, Item 1) service valves.
9. Perform Check Compressor Oil Level per this WP.
NOTE
When the compressor is off, the oil level will usually indicate slightly higher than it
actually is. Previous operation can affect the temperature of the oil.
10. Repeat Step 9 procedure as required until compressor oil level is at the proper level.
11. Install top-middle panel (WP 0013, Install).
12. Install top-left panel (WP 0013, Install).
END OF TASK
END OF WORK PACKAGE
0016-8