TM 5-4110-204-13
panel is too saturated to dry out, the
(d) Apply epoxy mixture and patch material
insulation must be replaced in the panel.
from repair kit as specified.
T h e 1800J model refrigerator has
(e) Apply tape over the entire patch area and
polyurethane  insulation.
the panel is ready for use.
c. Installation Refer to paragraph 2-4, and install
(f) For damaged areas up to 144 sq. in., follow
the refrigerator panels.
above steps for use of repair kit, but apply epoxy to
cloth, nylon, or like type material which has been cut
3-31. Thermometer
to 2 to 3 inches greater in each direction of the hole to
be covered.
a. Removal. Refer to paragraph 2-5, and remove
(g) Affix the patch over the damaged area
the thermometer from the door panel.
(h) Tape the patch in vertical and horizontal
b. Installation Refer to paragraph 2-5 and install
directions so that the patch will not move while
the thermometer on the door panel.
curing. It will take approximately 2 hours for the
patch to adhere properly.
3-32. Drain Strainer
(2) Major Repairs.
a. Removal. Refer to figure 3-14, and remove the
(a) Obtain a metal plate large enough to cover
drain strainer.
the damaged area.
b. Intstallation. Refer to figure 3-14, and install the
(b) Apply a watertight sealer between the
drain strainer.
metal plate and the surface of the panel to be
repaired.
3-33. Slide Botts
(c) Press plate tightly against the panel, and
secure it with sheet metal screws.
a. RemovaL Remove the four screws that secure
NOTE
the slide bolts to the partition panels, and remove the
If the fiberglass insulation should become
slide bolts.
saturated with moisture due to leakage of
b. Installtion Position the slide bolts on the
the panel, the panel should be removed
partition panels, and secure them with four mount-
ing screws.
and the moisture baked out of it. If the
Figure 3-9. Walk-in door ha miles and striker latch removal, installation and adjustment.
Change 5
3-10