TM 5-4110-217-14
Table 3-2. Organizational Preventive Maintenance Checks and Services - Continued
Q - Quarterly
Q - Quarterly
Total man-hours required.
Total man-hours required
Corrective
Corrective
Sequence
Item to be inspected
Work
action
Sequence
Item to be inspected
Work
action
number
procedure
time
para
number
procedure
time
para
(M/H)
ref
(M/H)
ref
9
FUEL FILTER
3
SPARK PLUG
(Model RMP-J/1-1OG)
(Model RMP-J/1-1OG)
Tighten thumb nut if leaking.
0.2
3-10
Replace spark plug that has a
1.0
Clean a dirty filter element.
cracked insulator or burned
10
SIGHT
electrodes.  Clean and set
GLASS
spark plug gap to 0.025 inch.
Torque spark plugs to 25 to
NOTE
30 foot pounds. Replace lead
When checking compressor
which is frayed or broken.
sight glass oil level, check
Clean  and  tighten  lead
prior to start up. When unit is
connections.
operating, be sure unit has
4
AIR CLEANER
operated  long  enough  to
(Model RMP-J/1-1OG)
stabilize  pressures,  usually
Clean as required. This
0.2
3-5f
16-20 minutes.
service will vary from a few
days operation in compara-
Oil level should be halfway up
0.1
tively clean conditions to twice
sight glass.  Refer to Direct
a day in dusty conditions.
Support Unit for adding oil.
5
BREAKER POINTS
11
FUELTANK
(Model RMP-J/1-lOG)
(Model RMP-J/1-1OG)
Replace pitted or burned
1.6
3-43
Add fuel as required. Tighten
2.0
3-11
breaker points. Proper point
loose mounting. Replace
5-6
gap adjustment is 0.020 inch.
leaking fuel tank Replace cap
Check adjustment every 200
gaskets.
Clean fuel cap
hours of operation.
strainer.
6
ENGINE OIL LEVEL
12
OPERATION
NOISE
OR
(Model RMP-J/1-1OG)
VIBRATION
Add oil as indicated by the
0.2
3-65
During operation observe for
0.1
3-15
engine oil level indicator (dip-
any
unusual
noise
or
stick).
Refer  to  current
vibration.
lubrication order.
13
REFRIGERATION SYSTEM
7
DRIVE
Check visually and check with
0.2
BELTS AND ALTERNATOR
halide
detector
all
BELT
connections
of
the
Adjust belts to proper tension.
1.0
3-13
refrigeration system for leaks.
Replace  worn,  frayed  or
Check liquid line sight glass
cracked belts. If one belt is
for  air  bubbles  or  milky
badly worn, both belts must
appearance
Report
be replaced
deficiencies to Direct Support
Unit
8
GOVERNOR LINKAGE
14
ELECTRIC MOTOR
(Model RMP-J/1-1OCG)
(Model RMP-J/1-IOE)
Inspect and clean governor
0.6
3-30
Check and observe correct
0.1
2-11a;
linkage
AdJust
governor
starting and running of motor
3-15
system  for  correct  engine
speed.
Section IV. OPERATOR'S MAINTENANCE
servicing fuel filter Service fuel filter after each
3-9.
General.
100 hours of operation. Clean the element and
The instructions in this section are published for the
bowl with an approved cleaning solvent
information and guidance of the operator to maintain the
3-11.
Fuel Cap and Strainer Service.  (Model
refrigeration unit.
3-10.
Fuel Filter Service (Model RMP-J/1-10G)
RMP-J/1-10G)
Refer to figure 3-3 and service the fuel filter.
Refer to figure 3-4 and service the fuel tank cap and
strainer.
NOTE
NOTE
Be sure fuel shutoff valve is closed before
Service cap and strainer after each 500 hours
of operation. Clean the cap and strainer In an
approved cleaning solvent.
Change 3 3-6