TM5-4110-234-14
TO 40R7-5-7-1
4-63. CHOKE (F1OOOORG-2)
a. Access.
(1)
Be sure that the unit is turned off. If there is a chance that someone will turn it on, disconnect the battery.
(2)
Open the left side access door.
b. Adjust. (See figure 4-33).
This choke should not require any seasonal readjustment, but if adjustment becomes necessary proceed as follows:
Figure 4-33. Choke F10000RG-2
(1)
Pull choke lever up and insert a 1/16-inch (1.59 mm) diameter rod through shaft hole (opposite end from
lever) and engage rod in notch of mounting flange, to lock shaft in place.
(2)
Loosen the choke lever clamp screw.
(3)
With air inlet removed, adjust choke lever so carburetor choke plate is completely closed, or not more than
5/16-inch (7.94 mm) open.
(4)
Tighten choke lever clamp screw and remove locking rod from shaft.
c. Remove. (See figure 4-33).
(1)
Loosen the screw in the end of the swivel and remove the link.
(2)
Remove two mounting screws and pull the choke from the unit.
4-79
|