TM 5-4120-274-15
to the component or components. If a broken wire
the break in a wire is in a harness or inaccessible
is part of a wiring harness, disconnect the wire at
area, replace wire (e below).
each end and tape these ends with electrical tape.
Install a new wire and attach it to the outide of
connecting each end from the component or com-
the wiring harness.
ponents to which it is connected. Touch the test
probes of a multimeter to each end of the wire.
5-23. Tubing and Fittings
If continuity is not indicated, the wire is defec-
The refrigerant piping used on the air condition-
tive and must be repaired or replaced.
ing units consists of copper tubing and necessary
d. Repair. Remove the insulation on the wire
fittings. Joints of refrigeration pipes and fittings
to expose one-half inch of bare wire at both ends
are soldered. Inspect the piping and fittings for
of the break. Twist bare wire together and solder
the connection. Cover the repaired break with elec-
cracks and breaks. (para 3-45b). Replace defec-
trical tape and friction tape. Do not leave any bare
tive pipes with those of the same length, size,
wire exposed. If a terminal lug breaks off a wire,
ing items such as the thermostatic expansion
replace it, using an exact duplicate terminal lug.
valves, or solenoid valves, disassemble valves and
e. Replacement. Replace a wire by disconnect-
wrap valve bodies with a damp cloth to protect
ing it from the component or components and re-
them from damage by heat.
move the wire. Install a new wire and connect it
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |