TM 5-4120-341-13
REMARKS
LOCATION/ITEM
ACTION
If the compressor is mechanically frozen or
a.
8. Compressor Burnout Procedure
has sustained a motor burnout, "replace the
compressor.
Flush out the entire refrigeration system as
b.
follows or repeated burnouts will occur.
refrigerant system.
(2) P u r g e refrigerant system with dry
nitrogen (paragraph 5-8).
removed,
purge
(4) With
compressor
refrigerant system with dry nitrogen
(5) Install new compressor.
(7) Discharge refrigerant system three (3)
times (paragraph 5-8).
(8) Start and operate air conditioner for
twenty-four (24) hours (paragraph 2-12).
(9) Stop air conditioner (paragraph 2-14).
(10) Discharge refrigerant system and purge
with dry nitrogen (paragraph 5-8).
(12) Discharge refrigerant system and
recharge with refrigerant (paragraph
(13) Operate air conditioner.
|