TM 5-4120-356-14
e.
J u n c t i o n Box.
(1) Inspection.
I n s p e c t the junction box for burn-out and for any damage
w h i c h would impair serviceability.
( 2 ) R e p l a c e . R e p l a c e the junction box in case of burn-out or damage which
would impair serviceability. Refer to steps (3) and (4) for removal and installation
of the junction box.
WARNING
D i s c o n n e c t the air conditioner from the
electrical power source before removing
the junction box or its components.
( 3 ) Removal.
( a ) Turn selector switch to "OFF" p o s i t i o n a n d d i s c o n n e c t t h e a i r
conditioner from the source of electrical power.
( b ) Remove the lower access panel, a i r i n t a k e g r i l l e a n d a i r f i l t e r .
(c) Refer to figure 3-12 and remove the junction box from the unit.
(4) Installation.
( a ) R e f e r t o f i g u r e 3 - 1 2 a n d i n s t a l l t h e j u n c t i o n box in the unit.
( b ) R e i n s t a l l t h e a i r f i l t e r , a i r i n t a k e grille and the lower access
panel on the air conditioner.
f. Fuses.
WARNING
D i s c o n n e c t the air conditioner from the
electrical power source before removing
fuses from the junction box.
( 1 ) Removal.
( a ) Turn selector switch to "OFF" p o s i t i o n a n d d i s c o n n e c t t h e a i r
conditioner from the source of electrical power.
(b) Remove the lower access panel from the air conditioner.
(c) Refer to figure 3-12 and remove panel (13) from the junction box.
(d) Refer to figure 3-13 and remove the three fuses from the junction
box .
(2) Test. (See figure 3-13.)
Replace any fuse which fails test.
(3) R e p l a c e .
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |