TM
5-4120-356-14
REFER TO PARAGRAPH 3-10e FOR PRELIMINARY STEPS IN THE REMOVAL OF THE JUNCTION BOX.
1.
2.
IF THE JUNCTION BOX IS TO BE REPLACED, REFER TO FIGURE 3-8 AND REMOVE THE CONTROL BOX. IF
THE JUNCTION BOX IS BEING PULLED OUT OF THE UNIT FOR MAINTENANCE PURPOSES ONLY, THE CONTROL
BOX MAY BE LEFT IN PLACE ON TOP OF THE JUNCTION BOX.
3. REMOVE FOUR SCREWS (4) AND SPACERS (12) AND PULL JUNCTION BOX OUT OF UNIT.
4.
DISCONNECT CONNECTOR PLUGS (1, 2).
IF CONTROL BOX HAS BEEN LEFT IN PLACE, DISCONNECT CON-
NECTOR PLUG (3).
5. REMOVE FOUR SCREWS (10) AND WASHERS (11) AND REMOVE PANEL (13) FROM JUNCTION BOX (15).
6. IF THE JUNCTION BOX IS BEING PULLED OUT OF THE UNIT FOR MAINTENANCE PURPOSES ONLY, THE CIR-
CUIT BREAKER CABLE MAY BE LEFT ATTACHED TO THE SIDE OF THE JUNCTION BOX.
7.
IF THE JUNCTION BOX IS TO BE REPLACED, REMOVE SCREW (5) AND SLIDE END FITTING (6) OFF END
OF CABLE (9). PULL ON KNOB (14) UNTIL CABLE (9) CLEARS CLAMPS (8).
INSTALLATION OF JUNCTION BOX
POSITION COVER (13) ON JUNCTION BOX (15) AND SECURE WITH FOUR SCREWS (10) AND WASHERS (11).
1.
2.
IF CIRCUIT BREAKER CABLE HAS BEEN REMOVED, THREAD CABLE (9) THROUGH CLAMPS (8) AND PLATE
(7). THREAD END OF FITTING (6) ONTO CABLE (9) AND SECURE WITH SCREW (5).
3.
CONNECT CONNECTOR PLUGS (1, 2). IF CONTROL BOX HAS BEEN LEFT IN PLACE ON JUNCTION BOX, CON-
NECT CONNECTOR PLUG (3).
4.
IF CONTROL BOX HAS BEEN REMOVED FROM JUNCTION BOX, REFER TO FIGURE 3-8 AND INSTALL CONTROL
BOX .
5. POSITION JUNCTION BOX IN UNIT AND SECURE WITH FOUR SCREWS (4) AND SPACERS (12).
6. REFER TO PARAGRAPH 3-10e FOR FINAL-STEPS IN INSTALLATION OF JUNCTION BOX.
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |