TM
5-4120-356-14
REFER TO PARAGRAPH 3-11 FOR PRELIMINARY STEPS IN REMOVING RFI FILTER ASSEMBLY.
1.
2. REMOVE EIGHT SCREWS (1) AND WASHERS (2) FROM PANEL (3).
3. PULL PANEL (3) AND ATTACHED RFI FILTER ASSEMBLY (4) OUT OF AIR CONDITIONER.
4. DISCONNECT ELECTRICAL PLUGS P10 (5) AND P11 (6) FROM RECEPTACLES J10 (8) AND J11 (9).
5. REMOVE SIX SCREWS (7) AND SEPARATE RFI FILTER ASSEMBLY (4) FROM PANEL (3).
INSTALLATION OF RFI FILTER ASSEMBLY
POSITION THE RFI FILTER ASSEMBLY (4) ON PANEL (3) AND SECURE WITH SIX SCREWS (7).
1.
2. CONNECT ELECTRICAL PLUGS P10 (5) AND P11 (6) TO RECEPTACLES J10 (8) AND J11 (9).
3. POSITION PANEL (3) WITH ATTACHED RFI FILTER ASSEMBLY (4) IN AIR CONDITIONER AND SECURE
WITH EIGHT WASHERS (2) AND SCREWS (1).
SCHEMATIC DIAGRAM
RFI FILTER ASSEMBLY TEST
CHECK FOR CONTINUITY BETWEEN PIN A
1.
OF J10 AND PIN A OF J11.
2. CHECK FOR CONTINUITY BETWEEN PIN B
OF J10 AND PIN B OF J11.
3. CHECK FOR CONTINUITY BETWEEN PIN C
OF J10 AND PIN C OF J11.
4. CHECK FOR CONTINUITY BETWEEN PIN D
OF J10 AND PIN D OF J11.
Figure 3-22. Removal, installation and testing of RFI filter assembly
|