|
|
TM 5-4120-356-14
(c) Apply high vacuum grease (NSN 9150-00-965-2408) or equivalent
to the seats of flare nut fittings.
( d ) Apply leak lock (NSN 4030-00-999-6313) to the t h r e a d s of threa-
ded fittings.
(e) Install the fittings and associated component and tighten fitt-
ings.
(4) Repressurize the system with vaporized refrigerant to get 100 psig
2
( 7 . 0 k s / m c ) on both sides (suction and discharge) of the compressor.
( 5 ) Using available leak detector, verify that the repaired area is no
longer leaking. Repeat steps (1) through (5) if the repaired area is still leaking.
e . I f r e f r i g e r a n t l e a k d e t e c t i o n a n d r e p a i r p r o c e d u r e s have been performed
as a result of the replacemento f r e f r i g e r a n t c o m p o n e n t o r c o m p o n e n t s , refer to, and
c o m p l e t e applicable installation procedures f o r t h e r e p l a c e d c o m p o n e n t o r c o m p o n e n t s .
f . I f r e f r i g e r a n t l e a k d e t e c t i o n a n d r e p a i r p r o c e d u r e s h a v e not been perform-
e d as a result of the replacement of refrigerant components, proceed as follows:
( 1 ) Release refrigerant from the system in accordance with paragraph 4-6.
( 2 ) Purge the refrigerant system in accordance with paragraph 4-8.
( 3 ) Evacuate the refrigerant system in accordance with paragraph 4-9.
( 4 ) C h a r g e t h e s y s t e m w i t h r e f r i g e r a n t i n a c c o r d a n c e with paragraph 4-10.
4-5.
Nearly all operations for the correction of malfunctions found in troubleshooting or
m a i n t e n a n c e activities of Direct Support Maintenance require that the refrigerant
system be opened. R e f e r to paragraphs 4-6 through 4-10 for procedures u s e d in open-
i n g and closing the refrigerant system.
S e e figure 4-1 for a flow diagram of the
r e f r i g e r a n t system.
O p e n i n g the refrigerant system for the replacement of components or other maintenace
a c t i v i t i e s requires the release of refrigerant from the system. Refer to figure 4-2
when releasing refrigerant.
4-7.
The dehydrator (drier) prevents the accumulation of moisture and contaminates within
t h e refrigerant system. T h e dehydrator must be replaced each time the system is ex-
posed to the atmosphere. R e l e a s e refrigerant in accordance with paragraph 4-6 be
f o r e removing the dehydrator from the system. Refer to figure 4-16 for replacement
o f the dehydrator.
The refrigerant system must be purged each time the system is exposed to the atmosphere.
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |