(j) Connect the recovery line to the tubing at point "D".
( k ) Start the pump and flush t h e line for approximately 10 minutes
then turn the pump off.
( l ) Switch the pump lines so t h a t the recovery line is connected to
t h e tubing at p o i n t "F" and the discharge line i s c o n n e c t e d t o t h e t u b i n g a t p o i n t " D " .
( m ) Start the pump and flush t h e line for approximately 10 minutes
t h e n turn the pump off.
( n ) Remove the discharge line from the tubing at point "D" and the
r e c o v e r y l i n e f r o m the tubing at point "F".
( o ) Cap the tubing at points "F" and `D", uncap the tubing at
p o i n t "E" and o p e n t h e v a l v e a t p o i n t " B " . "
( p ) Connect the discharge line to the tubing at point "E" and con-
nect the recovery line to the valve at point "B".
( q ) Start the pump and flush t h e line for approximately 10 minutes
then turn the pump off.
( r ) Switch the pump lines so t h a t the recovery line is connected to
t h e tubing at point "E" and the discharge line i s c o n n e c t e d t o t h e v a l v e a t p o i n t " B " .
( s ) S t a r t t h e p u m p a n d f l u s h t h e line for approximately 10 minutes
then turn the pump off.
( t ) Remove the discharge line from the valve at point "B" and close
--
the valve at point "B".
( u ) Remove the cap from the tubing at p o i n t "C" and connect the
discharge line to the tubing at point "C".
( v ) Start the pump and flush the line f o r approximately 10 minutes
t h e n turn the pump off.
( w ) Switch the pump lines so that the r e c o v e r y line is connected to
t h e tubing at p o i n t " C " a n d t h e d i s c h a r g e l i n e i s c o n n e c t e d t o t h e t u b i n g a t p o i n t " E " .
( x ) Start the pump and flush the line for approximately 10 minutes
t h e n turn the pump off.
( Y ) Refer to figure 3-12 and remove plug P3 from the junction box.
(z) Energize the pressure equalizer solenoid valve (12) by apply-
i n g 24 volts dc across pins E and F of plug P3.
( a a ) Remove the recovery line from the tubing at point "C" and cap
t h e tubing at point "C".
4-21