TM 5-4120-356-14
VIEW B. LIQU ID LINE SOLENOID VALVE LOCATION
REMOVAL OF LIQUID LINE SOLENOID VALVE
REFER TO PARAGRAPH 4-14b FOR PRELIMINARY STEPS IN REMOVAL OF LIQUID LINE SOLENOID VALVE.
1.
2. DISCONNECT ELECTRICAL PLUG (2) FROM VALVE.
CAUTION
THE LIQUID LINE SOLENOID VALVE MUST BE
DISASSEMBLED BEFORE DISCONNECTING THE
TUBING FROM THE VALVE BASE TO AVOID
HEAT DISTORTION.
REFER TO VIEW A AND DISASSEMBLE LIQUID LINE SOLENOID VALVE FROM BASE.
3.
4. DISCONNECT TUBING FROM BASE OF LIQUID LINE SOLENOID VALVE.
REMOVE TWO SCREWS (3) AND TWO WASHERS (4) AND REMOVE VALVE BASE FROM AIR CONDITIONER.
5.
INSTALLATION OF LIQUID LINE SOLENOID VALVE
POSITION LIQUID LINE SOLENOID VALVE BASE IN AIR CONDITIONER AND SECURE WITH TWO WASHERS
1.
(4) AND SCREWS (3).
CAUTION
BRAZE THE TUBING TO THE VALVE BASE BE-
FORE REASSEMBLING THE VALVE TO AVOID
HEAT DISTORTION.
TS5-4120-356-14/4-13
2. CONNECT TUBING TO VALVE BASE.
3. REFER TO VIEW A AND REASSEMBLE THE LIQUID LINE SOLENOID VALVE.
4. CONNECT ELECTRICAL PLUG (2).
5. REFER TO PARAGRAPH 4-14b FOR FINAL STEPS IN INSTALLATION OF LIQUID LINE SOLENOID VALVE.
|