(f) Refer to paragraph 4-10 and charge the system with refrigerant.
a.
R e f r i g e r a n t Tubing and Fittings
( 1 )  I n s p e c t .  R e f e r to figure 4-12 and inspect the r e f r i g e r a n t t u b i n g
a n d fittings for damage which would impair serviceability.
(2)
Test.
( a ) C h e c k r e f r i g e r a n t t u b i n g a n d f i t t i n g s f o r l e a k s in accordance
w i t h the procedures given in paragraph 4-4c.
( b ) R e p a i r a n y l e a k s f o u n d i n a c c o r d a n c e w i t h t h e procdures given
( 3 )  R e p l a c e .  R e p l a c e any tubing o r f i t t i n g s w h i c h are damaged to an
e x t e n t t h a t s e r v i c e a b i l i t y w o u l d b e i m p a i r e d ,  R e p l a c e m e n t procedures are as follows:
(a) Refer to figure 4-2 and release refrigerant from the system.
( b ) R e f e r t o f i g u r e 4 - 1 2 a n d r e m o v e t h e d e f e c t i v e t u b i n g and/or
fittings.
(c) Install replacement tubing and/or fittings.
( d ) Perform any further maintenance or refrigerant system compo-
nents
required.
(e) After tubing and fittings are replaced, purge the refrigerant
system in accordance with paragraph 48.
(f) Check the replaced tubing and/or fittings and the dehydrator
f o r leaks in accordance with paragraph 4-4c.
If any leaks are found, repair in
a c c o r d a n c e with the procedures given in paragraph 4-4d.
(g) Refer to figure 4-4 and evacuate the refrigerant system.
( h ) Charge the system with refrigerant in accordance with paragraph
4-10.
L i q u i d Line Solenoid Valve
b.
( 1 ) G e n e r a l .  Testing and repair of the liquid line solenoid valve is
accomplished at the oganizational maintenance level (refer to paragraph 3-13a).
(2) Removal.
( a ) R e f e r t o f i g u r e 42 and release refrigerant from the system.
( b ) R e f e r t o figure 3-12 and partially remove the junction box.
( c ) R e f e r t o f i g u r e 3-22 and remove the RFI filter panel to pro-
v i d e access to the liquid line s o l e n o i d v a l v e .