Preventative Maintenance Checks and Services
If the air conditioner must be kept in continuous operation, check
NOTE:
and service only those items that can be checked and services
without disturbing operation.  Make complete checks and services
when the air conditioner can be shut down.
B - Before Operation D - During Operation A - After Operation
FOR READINESS
PROCEDURES
REPORTING, EQUIPMENT
CHECK FOR AND HAVE
ITEMS TO BE
ITEM INTERVAL
IS NOT READY/
NO.  B D  A
INSPECTED
REPAIRED OR ADJUSTED
AVAILABLE IF
AS NECESSARY
With cover rolled up for
1
Condenser Fabric
Cover
air conditioner operation,
check securing ties for
damage.
Obstructions can not be
Inspect for obstruction
Condensate Drains
2
removed.
to drainage. Remove
obstruction.
Damage to connector pre-
Main Power Receptacle Check for secure power
3
vents satisfactory connec-
connection.  Tighten if
Connector
tion.
necessary.
Yellow indicates moisture;
Liquid Sight Indicator Check for moisture and
4.
bubbles or milky appear-
low refrigerant charge.
(Sight Glass)
ante indicates low charge.
(After unit has run for
a minimum of 2 hours.)
Any condition in proce-
Air Conditioner
Check for abnormal opera-
5
dures column is observed.
Operation
tion vibration, unusual
noise, failure to respond
to controls.
Information Plates
Missing or damaged.
6
Missing, damaged, no
7
Covers
mildew.  All snaps in
good condition. Cover
must be rolled and
stored on top of unit
during operation.
Panels
No major dents or cracks.
8
No missing or loose screws.
Grilles (Louvers)
No major dents or cracks.
9
No missing or loose screws.
Screens and Guards
No major dents or cracks.
10
No missing or loose screws.
11
Air
Filter
Check that filter is clean.
Condensate Drain
No water dripping any-
12
where except through
drain.
13
Control Module
Check that knobs are not
missing.