TM5-4120-383-14
4-8.
USE OF TROUBLESHOOTING TABLE.-Continued
The technicians should first find the malfunction symptom or
b.
unsatisfactory performance characteristic in the table which most
closely describes the immediate situation; then perform the test
and inspections, and corrective action steps in the order in which
they are listed.
c. This manual cannot list all possible situations which may be
encountered, nor can it list all test and inspection, and
If a condition is
corrective action steps which may be taken.
encountered which cannot be resolved within the capabilities and
experience of organizational maintenance personnel assistance
should be requested from direct support maintenance.
TROUBLESHOOTING
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
AIR CONDITIONER DOES NOT START IN ANY MODE.
Step 1.
Check if circuit breakers are tripped.
Reset circuit breakers.
Step 2.
Check if input power has been disconnected.
Connect input power.
Disconnect input power before performing
internal electrical troubleshooting. Voltages
used can be lethal.
If input power has been disconnected for an
unknown period of time, do not start in COOL
MODE until power has been reconnected for a
minimum of four hours.
Step 3.
Check for loose or damaged electrical connectors or
damaged wires in wiring harnesses.
|