TM5-4120-38314
TROUBLESHOOTINGContinued
Table 42.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Tighten or replace connectors, or repair damaged
wires.
Check that internal wiring at terminal board TB3 is
Step 4.
wired for connector to which input power is
connected.
See paragraph 4-4 and move wires if necessary.
(See para
Check for defective circuit breaker.
Step 5.
Replace circuit breaker if defective.
(See
Check for defective MODE SELECTOR switch.
Step 6.
Replace switch if defective.
2.
CONDITIONED (EVAPORATOR) AIR FAN DOES NOT START OR STOPS
DURING OPERATION IN ANY MODE.
Disconnect input power before performing
internal electrical troubleshooting. Voltages
used can be lethal.
(See para
Check operation of evaporator fan motor.
Step 1.
Test motor.
Replace motor if defective.
(See para
Check operation of MODE SELECTOR switch.
Step 2.
Test switch.
Replace switch if defective.
(See fig.
Check electrical connections and wiring.
Step 3.
4-4 and para 4-20.)
Tighten or replace connectors or repair or
replace damaged wires.
4-30
|