4-12.
SCREENS AND GUARDS.Continued
(2) Remove 2 each screws and lock washers from horizontal
frames of condenser air inlet guard.
NOTE
The 6 screws on the vertical frames of the condenser
air inlet guard secure the condenser coil to the air
conditioner housing.
(3) Remove 6 each screws and lock washers from vertical
frames and remove condenser air inlet guard.
Clean.
b.
(1) Usually it is only necessary to wipe or brush the dirt
from the guards.
Dry cleaning solvent (Fed Spec P-D-680) used to clean
parts is potentially dangerous to personnel and
Do not use near open flame or excessive
property.
Flash point of solvent is 100F to 138F (38C
heat.
to 59C).
(2) If the guards are extremely dirty, clean with a detergent
solution or dry cleaning solvent (Fed Spec P-D-680).
Refer requirements
Check for general condition.
Inspect.
c.
for repair or replacement to direct support maintenance.
Installation.
Secure the guards with screws and lock
d.
washers.
RETURN AIR LOUVER AND AIR FILTER.
The return air louver is located on the lower front of the unit.
(See
The air filter is clipped to the back side of the louver.
Removal.
a.
(1) Remove 8 screws and lock washers and pull louver from
unit.
(2) Remove filter from clips on back of louver.