TM5-4120-383-14
4-14.
SUPPLY AIR LOUVER.-Continued
(3) Agitate until dirt is removed, using a soft brush if
necessary to loosen caked-on dirt.
(4) Rinse in clean water or clean dry cleaning solvent.
(5) Dry thoroughly.
Inspect.
Check the louver for general condition.
c.
Bent
louvers can usually be straightened with the fingers. Refer
requirements for further repair or replacement to direct support
maintenance.
Apply a few drops of light oil to all pivot
d. Servicing.
points and bearing surfaces of louvers. Wipe or blot up all excess
oil with a cloth.
Secure louver with screws and lock washers.
Installation.
e.
INFORMATION PLATES.
See figure 2-3 for location and information contained on Warning
If any plates are missing, damaged, or
and instruction plates.
illegible, they should be replaced. Refer replacement to direct
support maintenance.
MIST ELIMINATOR.
The mist eliminator traps moisture blown from the evaporator coil.
It is located below the top front cover, between the evaporator
(See fig. 4-12.)
coil and the supply air louver.
Removal.
a.
(1) Disconnect power at power source.
(2) Remove eight screws and top front cover.
(3) Pull mist eliminator up and out of mounting frame.
446
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |