Click here to make tpub.com your Home Page

Page Title: HEATER THEMOSTAT. (Cont)
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM5-4120-383-14
4-34.
HEATER
THERMOSTST.-Continued
(8) Repeat step (7) with meter connected to terminals 3
and 4.
(9) Tape the bulb of a thermometer or junction of a
thermocouple to the body of the heater thermostat, and connect the
multimeter to terminals 1 and 2 .  Use a 150 watt lamp bulb or a
heat source.  Gradually apply heat while observing both the
thermometer and the multimeter.  Continuity should drop out at 145
to 155F (63 tO 68C).  Remove heat source and let the thermostat
cool while observing the thermostat and multimeter.  Continuity
should be re-established at 100 to 120F (38 to 49C).
(10) Repeat step (9) with meter connected to terminals 3
and 4.
b.
Replace.
Replace heater thermostat if defective.
Installation.
c.
(1) See tags and wiring diagram figure 4-4 and connect leads.
Remove tags.
(2) Attach thermostat to bracket with two screws and lock
washers.
(3) Attach thermostat and bracket assembly to flange of the
top center cover with two screws.
(4) Install top front cover (para 4-11).
(5) Connect power at power source.
HEATER ELEMENTS.
The heater elements are located in the upper front compartment
behind the evaporator coil.
Disconnect input power from the air conditioner
before performing maintenance on any part of the
electrical system.  The voltages used can be lethal.
a.
Inspect/Test.
(1) Disconnect power at power source.
4-95

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business