TM5-4120-383-14
4-36.
CONDENSER FAN, MOTOR, AND HOUSING.-Continued
(7) If motor is to be repaired or replaced remove it from
mounting plate by removing four cap screws and hardware.
(8) Refer motor repairs to direct support maintenance.
NOTE
The impeller fan and condenser fan housing must be
removed together as follows.
(9) Remove three screws and washers, and fan inlet ring.
Use care not to break refrigeration tubing.
(10) Remove three screws, lock washers, washers, and loop
clamps that secure charging valves, pressure relief valve, and
tubing to condenser fan housing.
(11) Remove screw, lock washer, and loop clamp holding push-
pull control cable assembly to fan housing.
(12) Loosen screw in mechanical post to release push-pull
control cable assembly from louver assembly connecting link.
(13) Remove push-pull control cable assembly from fan housing
bracket by removing one casing nut.
(14) Remove eight screws, lock washers, and condenser air
inlet guard (para 4-12).
(15) Remove four screws, lock washers, two screw snaps, and
louver assembly (para 4-17).
(16) Remove five screws attaching condenser fan housing to
Screws are accessible from underneath the unit.
unit.
(17) Carefully remove condenser fan housing (with fan inside)
by rotating housing 90 counterclockwise and pulling straight out.
(18) Separate impeller fan from condenser fan housing.
d. Replace.
Replace all defective components found during
inspection and test.
Installation/Assembly.
e.
(1) Place impeller fan in condenser fan housing.
4-101
|