TM5-4120-383-14
4-36.
CONDENSER FAN, MOTOR, AND HOUSING.-Continued
(2) Carefully place condenser fan housing in unit by rotating
housing 90 counterclockwise and sliding into place.
(3) Secure condenser fan housing to unit with five attaching
screws.
(4) Install louver assembly and secure with four screws and
lock washers, and two screw snaps (para 4-17).
(5) Install condenser air inlet guard and secure with eight
screws and lock washers (para 4-12).
(6) Slide push-pull control cable through condenser fan
housing bracket, casing nut, and into mechanical post on louver
assembly connecting link.
(7) Tighten casing nut to secure push-pull control assembly
See paragraph 4-17 for cable
to condenser fan housing bracket.
adjustment before tightening screw in mechanical post.
(8) Secure push-pull control cable assembly to side of
condenser fan housing with screw, lock washer and loop clamp.
(9) Secure charging valves, pressure relief valve, and
refrigeration tubing to condenser fan housing with three loop
clamps, screws, washers, and lock washers.
(10)
Install fan inlet ring and secure with three screws and
washers.
(11) Slide motor shaft extension into hub of impeller fan and
secure with setscrew.
After bringing motor mounting bolts up snug, tighten
one full turn on each of the four bolts to compress
grommets flange by .06 inches.
(12) Insert four bushings and grommets into four motor
mounting holes and attach motor to mounting plate with eight flat
washers, four lock washers, and four cap screws.
(13)
Carefully place motor and mounting plate down into unit
and align holes in motor mounting plate with those in unit.
(14)
Install four cap screws and washers in motor mounting
plate but do not tighten them all the way.