4-36.
CONDENSER FAN, MOTOR, AND HOUSING.-Continued
(15) Slide motor shaft extension onto motor shaft and secure
with two setscrews.
(16) Spin fan by hand and check for equal clearance between
the inlet ring and outer edges of fan. Adjust mounting plate as
necessary.
(17) Tighten cap screws in motor mounting plate and check that
fan rotates freely and has adequate clearance.
(18) Connect P4, P5, P6, P8, and P9 connector plugs and secure
cable and harnesses with new plastic tie down straps or lacing
cord.
(19) Install three top covers (para 4-11).
(20) Connect power at power source.
EVAPORATOR COIL (CLEANING).
The evaporator coil is located in the upper front section of the
air conditioner.
(See fig. 4-33.)
Evaporator Coil
|