TM5-4120-383-14
4-38.
SOLENOID VALVE (COIL REMOVAL).-Continued
Disconnect input power from the air conditioner before
performing maintenance on any part of the electrical
The voltages used can be lethal.
system.
NOTE
The following basic instructions apply to both the
by-pass solenoid L1 and the pressure equalizer
solenoid L2.
Test.
a.
(1) Disconnect power at power source.
(2) Remove fabric cover (para 4-10) and top rear cover (para
(3) Disconnect the solenoid valve connector plug. P8 for L1
solenoid and P9 for L2 solenoid.
(4) Use continuity tester or multimeter set on lowest OHMS
scale to check for continuity between pins A and B in each
connector plug.
If continuity is not found, the coil is open and
must be replaced.
(5) Check for continuity between each pin in connector plug
If continuity is found the coil is grounded and
and coil casing.
should be replaced.
(6) If continuity checks are satisfactory apply 24 volts dc
from an external power supply across pins A and B in connector
Listen for a sharp click when the valve changes position.
plug.
If a click is not heard, internal valve problems are indicated and
Refer to direct support
the entire valve should be replaced.
maintenance.
b. Repair.
The only authorized repair to solenoid valve is
coil replacement.
The coil can be replaced without opening the
refrigeration pressure system.
Do not attempt any disassembly of the solenoid valve
other than coil removal with a refrigerant charge in
the system. Refrigerant will be sprayed out
dangerously if the screws that attach the tube and
plunger assembly to the valve body are loosened.