TM5-4120-383-14
5-2.
USE OF TROUBLESHOOTING TABLE.-Continued
Use great care to avoid contact with liquid
refrigerant or refrigerant gas being discharged from
Sudden and
any container under pressure.
irreversible tissue damage can result from freezing.
Wear thermal protective gloves and a face protector
or safety glasses in any situation where skin or eye
contact is possible.
Prevent contact of refrigerant gas with flame or hot
metal surfaces.
Heat causes the refrigerant to break down and form
carbonyl chloride (phosgene), a highly toxic and
corrosive gas.
Never pressurize lines with oxygen, mixture with oil
will cause an explosion.
TROUBLESHOOTING
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
High voltage can kill.
1.
COMPRESSOR WILL NOT START.
NOTE
Be sure and check Item 1, Steps 1 through 6,
Table 4-2 Troubleshooting for organizational
maintenance before proceeding with Step 1.
Step 1.
Check that the COMPR CIRCUIT BKR is ON.
Reset to ON position.
If circuit breaker will
not remain ON, check and/or replace.
(See para
4-25.)