TM5-4120-383-14
5-5.
TOP
COVERS.-Continued
Acetone and methyl-ethyl ketone (MEK) are flammable
and their vapors can be explosive. Repeated or
prolonged skin contact or inhalation of vapors can be
Use a well-ventilated area, wear gloves, and
toxic.
keep away from sparks or flame.
(3) Soften and remove old adhesive and gasket residue, using
acetone or methyl-ethyl ketone (MEK) and a stiff brush.
(4) Coat mating surfaces of metal and gasket with adhesive.
Let both surfaces air dry until adhesive is tacky but will not
stick to fingers.
(5) Starting with an end, carefully attach gasket to the
Press into firm contact all over.
metal.
(6) Minor dents and bent edges can be straightened using
common sheet metal repair procedures.
(7) Should touch up or refinishing be necessary see TM 43-
0139.
b. Replace.
Replace panels that are badly dented, bent, or
punctured.
SCREENS, GUARDS, AND LOUVERS.
For removal, cleaning, servicing, inspection and installation see
The only authorized repairs are replacements of
a. Repair.
gaskets and the straightening of bent blades.
NOTE
An initial supply of adhesive is supplied as Item 2,
Section II, Expendable Supplies and Materials List.
(See Appendix E.)
(1) Remove as much old gasket material as possible by pulling
or scraping it away from the metal surface.
5-13
|