TM5-4120-383-14
OVERHEATING CHECKS.
Overheating of the refrigeration system is often the cause of
bubbles appearing in the sight glass, or a reduction in cooling
Adequate cooling of the hot, compressed refrigerant
capacity.
vapor in the condenser is essential to the proper operation of the
air conditioner. The following checks should be made to ensure
that overheating is not the cause of the symptoms before
troubleshooting the pressurized portion of the refrigeration
system:
a.
Be sure there is no external obstruction to air flow into
the condenser intake screen and out of the condenser fan guard.
Be sure there is no obstruction within the intake screen and
b.
fan guard.
Be sure there are no obstructions or an excessive build-up
c.
of dust and dirt in the condenser coil.
NOTE
Addition of paint on coils will cause an insulation
and retardation of heat transfer.
REFRIGERANT PRESSURE CHECK.
5-19.
Except in cases where it is obvious that the refrigerant charge has
been lost, the first step in troubleshooting problems in the
refrigeration system should be to check discharge and suction
Check pressures as follows:
pressures under operating conditions.
a.
Turn MODE SELECTOR switch to OFF.
Remove charging valve access cover.
b.
c. Connect individual pressure gages or a refrigeration
servicing manifold and hoses to high (discharge) and low (suction)
charging (service) valves.
Take care that only a very small amount of
refrigerant is allowed to escape during hose purging.
Loosen hose connections at gages or charging
d.
manifold.
5-42
|