5-19.
REFRIGERANT PRESSURE CHECK.-Continued
NORMAL OPERATING PRESSURES
Temperatures
Pressure Range (psig)
Outdoor Ambient 55F(12.8C) 75F(24C)
100F(38C) 125F(51.7C)
90F(32C)
70-80
60-70
80-95
62-72
Return Air to
Suction
Suction
Suction
Suction
Unit (Dry Bulb) 205-220
400-425
305-325
225-245
Discharge
Discharge
Discharge
Discharge
80F(27C)
60-70
65-75
60-70
70-80
Return Air to
Suction
Suction
Suction
Suction
Unit (Dry Bulb) 185-205
290-310
215-235
385-415
Discharge
Discharge
Discharge
Discharge
The evaporator coil is located in the upper right front section of
(See fig. 5-9.)  For cleaning instructions
the air conditioner.
and inspection of installed items see paragraph 4-37.
Removal.
a.
Disconnect input power from the air conditioner
before performing maintenance on any part of the
electrical system.  The voltages used can be lethal.
(1) Disconnect power at power source.
(2) Remove eight screws and top front cover.
(3) Remove six screws, lock washers, and supply air louver.
(4) Remove mist eliminator by lifting out of unit.