1-6. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS.-Continued
J U N C T I O N B O X A N D C O N T R O L P A N E L M O D U L E. Contains major unit
See items 9 thru 16 for a description of some of these
controls.
controls.
Protects
control
circuit.
CONTROL CIRCUIT BREAKER.
Connection point
INPUT POWER RECEPTACLE (PRIMARY LOCATION).
See item 36 for alternate receptacle.
for
main input power cable.
Contains switches and controls for
CONTROL PANEL MODULE.
See items 13, 14, and 16 for a
operating the air conditioner.
description of these switches and controls.
This switch is
HIGH REFRIGERANT PRESSURE CUTOUT SWITCH.
factory set to shut the compressor off if the refrigerant discharge
l i n e p r e s s u r e r i s e s t o 4 3 5 t o 4 5 5 p s i g ( 3 0 . 5 8 t o 3 1 . 9 9 k g / c m2 ) .
NOTE
This switch must be hand reset-after
the
pressure
2
drops to 320 p s i g ( 2 2 . 5 0 k g / c m ) .
Protects
the
COMPR CIRCUIT B K R ( C o m p r e s s o r C i r c u i t B r e a k e r ) .
compressor.
MODE SELECTOR SWITCH.
Allows
selection
of
unit
operating
mode.
LOW REFRIGERANT PRESSURE CUTOUT SWITCH.
This switch is
factory set to shut the compressor off if the refrigerant suction
This
l i n e p r e s s u r e d r o p s t o 1 0 t o 2 0 p s i g ( 0 . 7 0 3 t o 1 . 4 0 6 k g / c m2 ) .
switch must be hand reset after the pressure rises above 40 psig
( 2 . 8 1 2 k g \ c m2 ) .
TEMPERTURE SELECTOR (THERMOSTAT) SWITCH.
This switch allows
selection of the desired temperature while operating in the cool or
heat modes.
GROUND CONNECTION POINT.
Shelter
or
van
electrical
ground
connection point.
CONDENSER DISCHARGE AIR LOUVER ASSEMBLY.
This louver
assembly is automatically controlled by the actuating cylinder,
item 38.
CONDENSER AIR INLET GUARD.
This
expanded
metal
screen
protects the condenser from damage.
FRESH AIR VENTILATION GUARD.
Screens
and
filters
fresh
air
entering the unit.