TM5-4120-384-14
LOCATION AND DESCRIPTION OF MAJOR COMPONENTS. - C o n t i n u e d
1-6.
NOTE
The air conditioner can be equipped for operation in
chemical-biological-radiological (CBR) environment by
connecting filtering equipment to the fresh air
filter.
This safety valve opens when the refrigerant
d i s c h a r g e l i n e p r e s s u r e r i s e s a b o v e 5 4 0 p s i g ( 3 7 . 9 7 k g / c m2 ) .
CHARGING VALVE, REFRIGERANT SUCTION LINE. Provides a
connection point for charging and checking suction line pressure.
Provides a
CHARGING VALVE, REFRIGERANT DISCHARGE LINE.
connection point for charging and checking discharge line pressure.
This valve is normally
SOLENOID VALVE, PRESSURE EQUALIZING.
open when the compressor is NOT running to equalize the pressure at
It closes when
the suction and discharge sides of the compressor.
the compressor starts.
This fan and motor draws outside
CONDENSER FAN AND MOTOR.
air over the condenser coil to remove heat from the refrigerant
passing through the tubes of the condenser coil.
COMPRESSOR.
Consists of a reciprocating compressor driven by
an electrical motor, hermetically sealed inside a steel container
An external (crankcase) heater is
with a lifetime charge of oil.
The purpose of the
attached to the lower part of the container.
heater is to prevent possible damage to the compressor caused by
liquid refrigerant accumulation in the cylinders during a period of
The heater is connected directly to input power and is
shut down.
thermostatically controlled to prevent overheating.
CONDENSER
COIL.
Made up of interconnected parallel copper
tubes retained in a series of multiple, closely spaced aluminum
This coil serves as a heat exchanger to remove the heat from
fins.
the compressed refrigerant vapor so that it will condense into a
liquid.
DESICCANT,
REFRIGERANT
(FILTER/DRIER).
Removes
moisture and contaminants from the refrigerant.
RECEIVER.
The
receiver
acts
as
a
storage
tank
for
the
liquid
refrigerant.
This valve is normally open
S O L E N O I D VALVE, LIQUID LINE.
when the compressor is NOT running and is thermostatically
controlled during cooling cycles when operating in the COOL mode.
1-7
|