1-6. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS.-Continued
These  valves  regulates  the
suction  pressure  by  recirculating  a  part  of  the  compressor
discharge  hot  gas  to  the  suction  line  when  the  suction  pressure
This  action  prevents  frosting  of  the
drops  below  a  preset  value.
evaporator  coil.
EXPANSION VALVE.
Meters  refrigerant  flow  to  the
evaporator
during cooling cycles when operating in the COOL mode.
EVAPORATOR COIL.
Similar  in  construction  to  the  multiple-
This  coil  serves  as  a  heat  exchanger
tube,  finned  condenser  coil.
for  the  refrigerant  to  absorb  heat  from  the  room  or  enclosure  air
circulated  through  the  evaporator  section.
HEATING ELEMENTS.
Consists  of  two  banks  of  heating  elements.
Both  banks  operate
Only one bank operates in the "LOW HEAT" mode.
i n  t h e  "HIGH HEAT" mode.
One bank shuts off when the thermostat is
satisfied in both HIGH and LOW HEAT modes.
MIST ELIMINATOR.
The  purpose  of  the  mist  eliminator  is  to
trap  droplets  of  condensed  water  from  the  evaporator  so  that  they
will  not  be  blown  into  the  air  conditioned  space.
INPUT POWER RECEPTACLE (ALTERNATE LOCATION). The main power
See  item  10  for  primary  location.
cable  may  be  connected  here.
See  installation  instructions  for  switch  over  instructions  if  this
power  receptacle  is  used.
REFRIGERANT SIGHT GLASS.
Visually  indicates  the  condition
of
the  refrigerant  flowing  in  the  refrigerant  lines  during  cooling
cycles when operating in the COOL mode.
ACTUATING CYLINDER.
This  hydraulic  cylinder  operates
I t  w i l l  s t a r t  t o  o p e n2 t h e  l o u v e r
discharge  louver  assembly.
assembly  at  150  to  180  psig  (10.55  to  12.66  kg/cm  )  and
fully open
2
louver  assembly  at  220  to  260  psig  (15.74  to  18.28  kg/cm )
compressor  discharge  pressure  to  allow  unit  operation  when  outside
temperature is low.
RESTRICTOR.
Divides  the  expanding
refrigerant
to
three
circuits  of  the  evaporator  coil.
1-8