TM5-4120-384-14
1-6. LOCATION AND DESCRIPTION OF MAJOR COMPONENTS.-Continued
These valves regulates the
suction pressure by recirculating a part of the compressor
discharge hot gas to the suction line when the suction pressure
This action prevents frosting of the
drops below a preset value.
evaporator coil.
EXPANSION VALVE.
Meters refrigerant flow to the
evaporator
during cooling cycles when operating in the COOL mode.
EVAPORATOR COIL.
Similar in construction to the multiple-
This coil serves as a heat exchanger
tube, finned condenser coil.
for the refrigerant to absorb heat from the room or enclosure air
circulated through the evaporator section.
HEATING ELEMENTS.
Consists of two banks of heating elements.
Both banks operate
Only one bank operates in the "LOW HEAT" mode.
i n t h e "HIGH HEAT" mode.
One bank shuts off when the thermostat is
satisfied in both HIGH and LOW HEAT modes.
MIST ELIMINATOR.
The purpose of the mist eliminator is to
trap droplets of condensed water from the evaporator so that they
will not be blown into the air conditioned space.
INPUT POWER RECEPTACLE (ALTERNATE LOCATION). The main power
See item 10 for primary location.
cable may be connected here.
See installation instructions for switch over instructions if this
power receptacle is used.
REFRIGERANT SIGHT GLASS.
Visually indicates the condition
of
the refrigerant flowing in the refrigerant lines during cooling
cycles when operating in the COOL mode.
ACTUATING CYLINDER.
This hydraulic cylinder operates
I t w i l l s t a r t t o o p e n2 t h e l o u v e r
discharge louver assembly.
assembly at 150 to 180 psig (10.55 to 12.66 kg/cm ) and
fully open
2
louver assembly at 220 to 260 psig (15.74 to 18.28 kg/cm )
compressor discharge pressure to allow unit operation when outside
temperature is low.
RESTRICTOR.
Divides the expanding
refrigerant
to
three
circuits of the evaporator coil.
1-8
|