2 - 6 . OPERATIONAL CHECKS.-Continued
If a knocking or pounding noise is heard when the
compressor  starts  in  the  following  check,  immediately
turn the MODE SELECTOR out of the COOL position.
Leave input power connected and wait at least two
hours before attempting another start in COOL mode. Damage to equipment
may result if personnel fail to observe precautions.
k.
Turn the TEMPERATURE SELECTOR control knob to the fully
W A R M E R  ( c l o c k w i s e )  p o s i t i o n ,  then turn the MODE SELECTOR switch to
COOL .
Note  that  the  evaporator  and  condenser  fans  start
immediately  and  that  the  compressor  starts  approximately  30  seconds
later.
Hold  your  hand  in  the  airflow  from  the  conditioned  air
supply  louver:  there should be no change in temperature.
Now turn
the TEMPERATURE SELECTOR control knob to the fully COOLER
(counterclockwise)  position  and  feel  the  supply  air  temperature
begin  to  drop  almost  immediately.  Leave  controls  in  the  present
position  and  perform  the  next  check.
l.
After  15  minutes  of  operation  check  the  sight  glass  to
determine  the  refrigerant  condition.
The  sight  glass  is  equipped
with  a  center  indicator  that  is  moisture  sensitive.
Dry
refrigerant  is  indicated  by  green,  it  turns  to  chartreuse  when  the
moisture  content  becomes  undesirable,  and  to  yellow  when  the  level
becomes  unacceptable.
Excessive  moisture  in  the  refrigerant  may
damage  or  possibly  destroy  the  compressor.
If  the  liquid
refrigerant  observed  in  the  sight  glass  has  a  milky  appearanc,  or
frequent  bubbles  appear,  the  volume  of  refrigerant  is  low  and  the
system should be charged.
Either  moisture  or  low  charge
indications  should  be  reported  to  direct  support  maintenance  for
appropriate  refrigeration  system  action.
D O not  operate  the  air  conditioner  in  the  COOL  mode
if  the  refrigerant  color  has reached the yellow band
or  if  numerous  bubbles  appear  in  the  sight  glass.
COOL mode operation may be continued with the
refrigerant  color  in  the  chartreuse  band  or  with  only
an  occasional  bubble  appearing  in  the  window,  but  the
sight  glass  should  be  rechecked  after  each  four  hours
of  operation  to  insure  that  the  condition  has  not
become worse. Damage to the equipment may result if personnel
fail to observe precautions.
m.
Turn the MODE SELECTOR s w i t c h
to
OFF.
Observe
that
all
air
conditioner  functions  cease.
Change 1 2-11