TM5-4120-384-14
2 - 6 . OPERATIONAL CHECKS.-Continued
If a knocking or pounding noise is heard when the
compressor starts in the following check, immediately
turn the MODE SELECTOR out of the COOL position.
Leave input power connected and wait at least two
hours before attempting another start in COOL mode. Damage to equipment
may result if personnel fail to observe precautions.
k.
Turn the TEMPERATURE SELECTOR control knob to the fully
W A R M E R ( c l o c k w i s e ) p o s i t i o n , then turn the MODE SELECTOR switch to
COOL .
Note that the evaporator and condenser fans start
immediately and that the compressor starts approximately 30 seconds
later.
Hold your hand in the airflow from the conditioned air
supply louver: there should be no change in temperature.
Now turn
the TEMPERATURE SELECTOR control knob to the fully COOLER
(counterclockwise) position and feel the supply air temperature
begin to drop almost immediately. Leave controls in the present
position and perform the next check.
l.
After 15 minutes of operation check the sight glass to
determine the refrigerant condition.
The sight glass is equipped
with a center indicator that is moisture sensitive.
Dry
refrigerant is indicated by green, it turns to chartreuse when the
moisture content becomes undesirable, and to yellow when the level
becomes unacceptable.
Excessive moisture in the refrigerant may
damage or possibly destroy the compressor.
If the liquid
refrigerant observed in the sight glass has a milky appearanc, or
frequent bubbles appear, the volume of refrigerant is low and the
system should be charged.
Either moisture or low charge
indications should be reported to direct support maintenance for
appropriate refrigeration system action.
D O not operate the air conditioner in the COOL mode
if the refrigerant color has reached the yellow band
or if numerous bubbles appear in the sight glass.
COOL mode operation may be continued with the
refrigerant color in the chartreuse band or with only
an occasional bubble appearing in the window, but the
sight glass should be rechecked after each four hours
of operation to insure that the condition has not
become worse. Damage to the equipment may result if personnel
fail to observe precautions.
m.
Turn the MODE SELECTOR s w i t c h
to
OFF.
Observe
that
all
air
conditioner functions cease.
Change 1 2-11
|