2 - 6 . OPERATIONAL CHECKS.-Continued
The
Turn the MODE SELECTOR switch to VENT (ventilate).
g.
Use  a  paper  streamer  or
evaporator  fan  should  start  immediately.
other  method  to  check  the  airflow  into  the  return  air  louver  and
out  of  the  conditioned  air  supply  louver.
To check maximum ventilation with fresh air, first turn the
h.
fresh  air  damper  control  wheel  to  fully  open  (down)  then  adjust  the
louvers  in  both  sections  of  the  return  air  louver  fully  closed.
Check  the  fresh  air  inlet  located  on  the  lower  left  corner  of  the
back  of  the  unit  using  a  paper  streamer  or  other  method  to  be  sure
that  air  is  being  drawn  in.
NOTE
For  maximum  ventilation  with  fresh  air,  it  is
necessary  that  room  or  enclosure  air  have  a  means  of
If  the  room  or
exit through an open door or window.
enclosure  is  tightly  closed,  an  overpressure  will
build  up  and  decrease  the  volume  of  fresh  air  drawn
in.
Fully
open
the
return
air
louvers
and
fully
close
the
fresh
i.
air  damper.
Turn the TEMPERATURE SELECTOR (thermostat) knob to the full
j.
Then turn the MODE SELECTOR switch to
WARMER  (clockwise)  position.
Place  your  hand  in  the  airflow  from  the  conditioned  air
LOW HEAT.
When  the  supply  air
supply  louver  and  feel  for  a  temperature  rise.
temperature  has  reached  a  relatively  stable  level,  turn  the  MODE
SELECTOR switch to HIGH HEAT and feel for a further temperature
Next, turn the TEMPERATURE SELECTOR thermostat control knob
rise.
Feel  that  supply
to  the  fully  COOLER  (counterclockwise)  position.
air  temperature  drops  to  approximately  the  same  relatively  stable
Finally, turn the MODE
level previously noted in LOW HEAT.
SELECTOR switch to LOW HEAT and feel the discharge air temperature
drop  to  ambient  level  (room  temperature).
NOTE
The  temperature  thermostat  control  has  an  effective
functional  range  between  60F  and  90F  (16C  and
32C).
In extreme conditions when ambient air
temperature  is  below  60F  (16C)  or  above  90F
(32C), the operation in either LOW HEAT or HIGH HEAT
mode  will  vary  from  that  described  above.