4 - 3 . SERVICE UPON RECEIPT OF MATERIAL.-Continued
NOTE
The unit weight (less shipping pallet) is 265 pounds
(120.0 kg) for F18H-3S, F18H-3SA and F18H-3SB.
Weight is 275 pounds (124.7 kg) for F18H-1S.
When
lifting or moving the unit on the shipping pallet, a
forklift may be used.
When lifting the unit into the
installation position a lifting hoist should be used.
(4) Remove Pallet.
Tilt the unit and pallet or raise the
unit using a forklift.
Remove the four bolts from the bottom of
the pallet.
Carefully lift the unit from the shipping pallet.
4-4.
Air
Conditioner
Preparation
For
Installation.
a.
(1) Two input power connectors are provided on the air
conditioner.
(See fig. 4-1.) Connector J1 is located on the front
of the air conditioner above the control panel module.
Connector
J11 is located on the rear of the air conditioner in the upper left
Determine which connector best suits your installation.
corner.
If power source is inside of conditioned area use J1.
If power
source is outside of conditioned area use J11.
(a) Air conditioners are shipped from the factory wired for
the use of the J1 power connector.
If this connector is used no
change is necessary.
(See fig. 4-2.)
(b)
If
the
J11
connector
is
to
be
used,
proceed
as
follows:
1 - Remove
top
(front)
cover
from
air
conditioner
2 D i s c o n n e c t wire
TB1.1-TB3.1
from
TB3
terminal
1
and
reconnect
to terminal 4.
3 D i s c o n n e c t wire
TB1.2-TB3.2
from
TB3
terminal
2
and
reconnect
to terminal 5.
(Not applicable to model F18H-1S.) Disconnect
wire
4
TB1.3-TB3.3 from TB3 terminal 3 and reconnect to terminal 6.
Install
top
(front)
cover
5
4-9
Change 2
|