Click here to make tpub.com your Home Page

Page Title: Table 4-1. ORGANIZATIONAL PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) QUARTERLY SCHEDULE
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM5-4120-384-14
Table
4-1.
ORGANIZATIONAL PREVENTIVE MAINTENANCE
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULE
Item to be
Procedures
Inspected/Serviced
4-13
Check  operation  of  louvers
1
a.
Return Air Louver
for  stiffness  or  binding.
b . Remove ,  c l e a n ,  i n s p e c t ,
repair,  and  lubricate  as
necessary.
Set  aside  for  the  present
and
c.
reinstall  after  item  4.
4-13
Remove,
clean,  inspect,
and
2
a.
Conditioned
Air
service
filter.
Filter
Discard  filter  and  obtain
re-
b.
placement,  if  damaged.
Place  filter
aside  for  the
c.
present  and
reinstall  after
item  4.
4-32
a . Wipe  or  vacuum  all  dust  or
3
Conditioned  Air
dirt  from  fan,  motor,  and  all
(Evaporator)  Fan
and Motor
other  components  and  surfaces
in  the  area.
b.
Inspect  fan  for  damaged  or
bent  blades,  the  motor  for
signs  of  overheating  and  all
mounting  hardware  for
tightness  and  security.
Inspect  wiring  harness  for
c.
damage or chafing and all
electrical  connections  for
tightness.
4-19
Check  for  loose  connections,
4
a.
Condensate Drain
missing  clamps,  indications  of
Tubing
water  leaks,  and  damaged  or
missing  tubing.
Repair  or  replace
as
b.
indicated.
4-22

Privacy Statement - Press Release - Copyright Information. - Contact Us