TM5-4120-384-14
Table
4-1.
ORGANIZATIONAL PREVENTIVE MAINTENANCE
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULEContinued
Item to be
I tem
Para
No.
Inspected/Serviced
Procedures
Ref.
c.
Install filter
and
return
air louver.
4-14
5
Conditioned Air
a.
Check operation of louvers
for
stiffness or binding.
Supply Louver
b.
Remove, clean, inspect,
repair, and lubricate as
necessary.
r.
Set aside for the present
and
reinstall after item 8.
6
Mist
Eliminator
4-16
a.
Remove, clean, and inspect
top front cover. Set aside for
present and reinstall after
item 8.
b.
Remove, clean, inspect, and
service mist eliminator.
Replace mist eliminator
if
c.
it is damaged.
d.
Set aside for the present
and
reinstall after item 8.
Compressed air used for
cleaning purposes will
not exceed 30 psi
( 2 . 1 k g / c m2 ) .
4-36
7
a. Blow accumulated dust and
Coil
dirt out of air passages in
evaporator coil using
compressed air or the
discharge side of a portable
vacuum cleaner. Blow from
front to back in opposite
direction from operational
airflow.
4-23
|