TM5-4120-384-14
4-16. MIST ELIMINATOR. - Continued
Dry cleaning solvent (Fed Spec P-D-680) used to clean
parts is potentially dangerous to personnel and
Do not use near open flame or excessive
property.
Flash point of solvent is 100F to 138F (38C
heat.
to 59C).
Skin, eye, and respiratory protection is
required to avoid injury to personnel.
b.
Clean.
(1) Immerse in
a
detergent
solution
or
dry
cleaning
solvent
(Fed Spec P-D-680).
(2) Agitate until dirt is removed,
using
a
soft
brush
if
necessary to loosen caked-on dirt.
(3)
Rinse
in
clean
water
or
clean
dry
cleaning
solvent.
(4)
Drain, then hold horizontal
and
tap
each
edge
on
bench
or
floor to
dislodge droplets.
c.
Inspect.
(1) Inspect for damage
such
as
perforations
or
punctures
in
the screen and aluminum.
(2)
Inspect
for
packed
or
crushed
material
that
would
reduce
airflow.
(3) Check for deformation
of
frame.
Straighten
if
possible
without crushing aluminum.
(4)
Replace
if
crushed,
punctured,
badly
deformed,
or
broken.
(5) Replace rubber insulation strip
across
top
of
mist
eliminator, if it is missing or damaged.
Installation.
d.
(1) TOP marking must be up and airflow arrows,
located
on
side
or bottom, must point outward away from coil.
(2) Slide mist eliminator down
into
mounting
frames
observing
air flow arrows and top marking.
Install top front cover and
(3) (Models F18H-3S and F18H-1S)
(Models F18H-3SA and F18H-3SB) Install
secure with twelve screws.
top cover. (See para 4-11.)
(4)
Connect
power
at
power
source.
4-48