4-17. CONDENSER AIR DISCHARGE LOUVER AND LINKAGE.
This louver is located at the right rear of the unit and is
automatically operated by a refrigerant pressure actuated cylinder
and connecting linkage.
The louvers open as refrigerant pressure
in the condenser coil increases.
This causes the louver to open
more fully to increase the flow of cooler air across the condenser
coil.
(See fig. 4-13.)
Clean/Inspect.
a.
(1)
Disconnect
power
at
power
source.
(2) (Models F18H-3S and F18H-1S)
Remove top rear cover (para
(Models F18H-3SA and F18H-3SB) Remove top cover (para
4-11) and condenser air inlet guard (para 4-12).
(3) The louver can be cleaned with a
soft
brush
or
washed
with
water and a mild detergent solution.
(4) Check louver for bent blades,
missing
or
damaged
gaskets,
and
missing hardware or bearings.
(5)
Clean
linkage
with
a
soft
brush
and
damp
rag.
(6)
Check
louver
linkage
for
tightness
and
smooth operation.
Adjustment.
b.
DANGEROUS C H E M I C A L i s u s e d i n t h i s e q u i p m e n t .
DEATH
or
severe
injury may result if personnel
fail
to
observe safety precautions.
Do not attempt to loosen or remove any o f
the
connections to the copper tubing.
Use great care to avoid contact with liquid refrig-
erant or refrigerant gas being discharged under
pressure.
Sudden and irreversible tissue damage can
result from freezing.
(1) Turn air conditioner off and wait four hours or until air
conditioner is uniform at an ambient temperature of less than 80F
(27C).
(2) Loosen two nuts
securing
actuating
cylinder
to
mounting
bracket (fig. 5-14).
4-49
Change 2
|