TM5-4120-384-14
4-31.1. (MODEL F18H-1S ONLY)
CAPACITORS - CONDENSER RUN (C-2), EVAPORATOR RUN (C-3), COMPRESSOR
START (C4), COMPRESSOR RUN (C-5) AND RELAY; COMPRRSSOR START (KS).
(Continued)
(3)
Remove
return
air
louver
Ground all capacitors before touching.
Touching the
terminals of a charged capacitor can cause electrical
shock and burns.
(4) Check that
wire
connections
and
terminals
are
tight
and
in
good condition.
(5) Check that
harness
wires
have
no
cuts,
broken
wires,
or
frayed insulation.
(6) Check
that
attaching
hardware
is
tight
and
in
good
condition.
(7) Inspect electrical parts for obvious damage such
as
cracks, evidence of overheating, and broken terminals.
(8)
Replace
all
damaged
or
broken
parts.
Test
Capactiors.
b.
(1) Check by placing test leads of ohmmeter on capacitor
terminals.
Ohmmeter needle should move rapidly toward the top of
the scale, then slowly return toward zero if the capacitor is good.
If needle moves to top of scale and remains there indicating an
internal short or if the needle does not move, indicating an open
circuit, replace the capacitor.
(2) Check capacitors for short circuits to case by placing
the positive (+) lead of the ohmmeter on the positive terminal of
the capacitor and the negative (-) lead to the case.
Continuity
should not be indicated.
Replace capacitor if bad.
Test
c.
(1) Using
a
check
terminals
1-5,
2-5,
and
1-2
for
(2)
If
exists
relay
is
good.
(3)
If
is
not
indicated,
replace
relay.
Change 2
4-90.3
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |