5 - 1 9 . REFRIGERANT PRESSURE CHECK.-Continued
(2)  If  discharge  pressure  is  low  and  suction  pressure  is
normal  (see  Table  5-3)  a  low  refrigerant  charge  is  indicated.
Table
5-3.
Pressure Range (psig)
Temperatures
125F(51.70C)
100F(380C)
75F(240C)
50F(100C)
O u t d o o r Ambient
78-88
65-75
60-70
55-65
90F(32C)
Suction
Suction
Suction
Suction
Return Air to
305-325
410-430
Unit (Dry Bulb)
220-240
190-210
Discharge
Discharge
Discharge
Discharge
60-70
70-80
55-65
53-63
80F(27C)
Suction
Suction
Suction
Suction
Return Air to
295-315
395-415
210-230
Unit (Dry Bulb)
180-200
Discharge
Discharge
Discharge
Discharge
(3)  If  discharge  pressure  is  normal  and  suction  pressure
is
either  high  or  low,  failure  or  maladjustment  of  the  pressure
regulator  valve  is  indicated.
(4)  If  discharge  pressure  is  high  and  suction
pressure
is
normal,  a  malfunction  of  quench  valve  is  indicated.
k.
When  pressure  tests  are
completed,
proceed
with
the
maintenance  action  indicated.