COMPRESSOR.-Continued
5-33.
Switch  the  pump  lines  so  that  the  discharge  line  is
connected  to  the  valve  at  point  3  and  the  recovery
line  is  connected  to  the  tubing  at  point  1.
Start  the  pump  and  flush  the  line  for
approximately
10 minutes, then turn the pump off.
Close  the  suction  line  service  valve  and  move  the
discharge  line  from  the  valve  at  point  3  to  the
tubing  at  point  2.
Start  the  pump  and  flush  the  line  for
approximately
10 minutes, then turn the pump off.
De-energize  the  bypass  solenoid  valve  by
disconnecting  the  dc  voltage  source  from  pins
A
and
B of plug P8.
Start  the  pump  and  flush  the  line  for
approximately
10 minutes, then turn the pump off.
Uncap the tubing at points 4 and 5.
Disconnect  the  pump  discharge  line  from  the  tubing
at  point  2  and  connect  it  to  the  tubing  at  point  5.
Disconnect  the  recovery  line  from  the  tubing  at
point  1  and  connect  it  to  the  tubing  at  point  4.
Cap the tubing at points 1 and 2.
Start  the  pump  and  flush  the  line  for
approximately
10 minutes, then turn the pump off.
Move the pump discharge line from the tubing at
Cap the tubing at
point  5  to  the  valve  at  point  6.
point  5.
Open
the
discharge
line
service
valve.
Start  the  pump  and  flush  the  line  for
approximately
10 minutes, then turn the pump off.
Switch  the  pump  lines  so  that  the  discharge  line  is
connected  to  the  tubing  at  point  4  and  the  recovery
line  is  connected  to  the  valve  at  point  6.
Start  the  pump  and  flush  the  line  for
approximately
10 minutes, then turn the pump off.
5-80