TM 5-4120-386-14
4-24. CONTROL MODULE-Continued.
REMARKS
LOCATION/ITEM
ACTION
Installation
Install connector with leads into
26. Connector
a.
With Leads
back plate.
(Wiring)
b. Connect leads and disconnect tags.
c. Install seven screws (53), seven
flat washers (55) and seven
locknuts (54) and secure connec-
tor to back plate.
d. Install screw (48), flat washer
(50), post spacer (52), locknut
(49), and clamp (51) and secure
temperature selector switch
sensing line to back plate.
Assembly
a.
27. Control
Add wire ties (69).
Push connector post through
Module
b.
front plate pressing on front
and back plates.
c. Attach three frame posts (57)
with three screws (56).
d . Attach temperature control
switch knob (8) by tightening
hex setscrew (9).
e. Slide cover (7) over module
and attach frame to cover with
four screws (5).
Installation
28. Control
Carefully push sensing bulb and
a.
line through slot in bottom of
Module
junction box.
Push control module straight
b.
into junction box.
Turn connector post screw
c.
clockwise until post is fully
engaged.
d.
Attach temperature selector
switch bulb atop evaporator
fan housing with clamps,
lockwashers, and screws.
See para 4-18.
Install evaporator inlet louver
e.
f.
Connect power.