TM 5-4120-386-14
Table 5-l. Direct support troubleshooting-Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4. COMPRESSOR RUNS BUT DOES NOT COOL
Step 1.
Check for excessively high temperature in conditioned area.
a. Close doors, windows or other openings.
b. Insulate areas of high heat gain.
Step 2. Check compressor for noisy operation, high suction pressure or
excessively low discharge pressure indicating leaky internal valves.
Replace compressor (Refer to paragraph 5-28.)
Step 3. Check liquid sight indicator for bubbles indicating low charge of
refrigerant.
a. Repair leaks or replace leaking component.
b. Purge and recharge system (Refer to paragraphs 5-11
and 5-15.)
Step 4. Check for high discharge pressure (Refer to table 5-2.)
Purge or bleed off excess refrigerant; check high-pressure
switch or pressure regulator valve.
5. COMPRESSOR EXCESSIVELY NOISY
Listen for knocking.
Step 1.
Check for high pressure indicating that liquid refrigerant is
returning to compressor (Refer to paragraph 5-16 and table
Step 2. Check for high discharge pressure, indicating overcharge of refrigerant
Purge or bleed off excess refrigerant; check high-pressure
switch or pressure regulator valve.
5-5