Click here to make tpub.com your Home Page

Page Title: Table 5-l. Direct support troubleshooting-Continued.
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-386-14
Table 5-l. Direct support troubleshooting-Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
6. SUCTION PRESSURE TOO LOW OR TOO HIGH
Stop compressor and check expansion valve as follows:
Step 1.
a. Remove remote bulb from well in suction line.
b. Place bulb in ice water for 1-2 minutes.
c. Start compressor.
Do not let liquid flood back into compressor or compressor will be
seriously damaged.
d. Remove bulb from ice water and hold it in one hand
to warm it. At the same time, check the suction
line for rapid change of temperature, which
indicates flood-through of liquid refrigerant. If
liquid floods through valve, it is operating
satisfactorily. If not, valve or remote bulb is
faulty.
e. Replace faulty expansion valve. (Refer to
Feel dehydrator for temperature difference. Discharge end will feel
Step 2.
cooler than input end if clogged, or discharged end may be frosty or
sweaty.
Replace dehydrator. (Refer to paragraph 5-17.)
7. LOW HEAT OR NO HEAT
Step 1.
Check heater wiring and control circuit for loose connections or broken
wires.
a. Tighten loose connections.
b. Replace or repair broken wires (Refer to paragraphs
4-33, 4-24 and 4-26.)
Step 2. Check continuity of mode selector switch and temperature selector
switch. (Refer to paragraph 4-24.)
5-6

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business