TM 5-4120-386-14
Table 5-l. Direct support troubleshooting-Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
7. LOW HEAT OR NO HEAT - Continued
Disconnect and remove heater elements, and apply 115-volt ac power
Step 3.
to check for open circuit in element. Element should heat.
Replace faulty heating elements (Refer to paragraph 4-33.)
Step 4. Check continuity of high-pressure cutout switch at room temperature.
Continuity should exist.
a. If continuity does not exist, press reset button and
recheck. (Refer to paragraph 5-23.)
b. Replace faulty switch.
Disconnect heater relay. Apply 24-28 volts dc to actuate relay and
Step 5.
check continuity at secondary terminals. Continuity should exist.
Replace faulty relay. (Refer to paragraph 4-25.)
Step 6. Check operation of evaporator fan and motor.
Repair or replace faulty fan or motor. (Refer to paragraphs
5-7
|