4120-01-238-4277">
|
|
TM 5-4120-393-14
Table 4-1. UNIT PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) QUARTERLY SCHEDULE (cont)
Item
Item To Be
No.
Inspected/Serviced
Procedures
e.
Turn mode selector switch to VENTILATE. Evaporator
fan should start.
f.
Use a paper streamer or smoke and note amount of air
being discharged from conditioned air outlet grille.
g.
Open fresh air damper fully.
h.
Close conditioned air intake grille louvers fully.
i.
Again check air flow as in step f. above. Air flow should
be approximately the same.
j.
Fully open louvers in conditioned air intake grille and
fully close fresh air damper.
k.
Turn TEMPerature control thermostat knob to fully
INCREASE (clockwise) position and then turn mode
selector switch to LO HEAT. Place your hand in air flow
at the center of the conditioned air outlet grille and feel
for a temperature rise. When discharge air
temperature has reached a relatively stable level, turn
mode selector switch to HI HEAT and feel for a further
temperature rise. Next, turn TEMPerature control
thermostat knob to fully DECREASE (counterclockwise)
position. Feel that discharge air temperature drops to
approximately same relatively stable level previously
noted in LO HEAT. Finally, turn mode selector switch
to LO HEAT and feel discharge air temperature drop to
ambient level.
NOTE
The TEMPerature control thermostat has
an effective functional range between 40 F
and 90 F (5 C and 32 C).
In extreme
conditions when ambient air temperature
is below 40 F (5 C) or above 90 F (32 C),
operation in either LO HEAT or HI HEAT
mode will vary from that described above.
4-33
|