Section V TROUBLESHOOTING
4-18. General. This section contains unit troubleshooting information for locating and correcting most of the operating
troubles which may develop in the air conditioner.
4-19. Troubleshooting. Each malfunction for an individual component is listed in table 4-2. The malfunction is followed
by a list of tests or inspections which help to determine probable causes and corrective actions to take. The tests or
inspections and corrective actions are to be performed in the order listed in the table. All malfunctions that may occur and
all tests or inspections and corrective actions may not be listed. If a malfunction is not listed or is not corrected by
corrective action, notify your supervisor.
NOTE
Before you use the table, be sure you have performed all applicable operating
checks (Table 4-1, item 20).
WARNING
HIGH VOLTAGE
is used in the operation of this equipment.
DEATH ON CONTACT
may result if personnel fail to observe safety precautions.
Never work on electrical equipment unless there is another person nearby who is
familiar with the operation and hazards of the equipment and who is competent in
administering first aid. When the technician is aided by operators, he must warn
them about dangerous areas.
Whenever possible, the input power supply to the equipment must be shut off
before beginning work on the equipment. Take particular care to ground every
capacitor likely to hold a dangerous potential.
When working inside the
equipment, after the power has been turned off, always ground every part before
touching it.
Be careful not to contact high-voltage connections of 208 volts ac input when
installing or operating this equipment.
Whenever the nature of the operation permits, keep one hand away from the
equipment to reduce the hazard of current flowing through vital organs of the
body.
Do not operate the equipment without all grilles, guards, louvers, and covers in
place and tightly secured.
Warning: Do not be misled by the term "low voltage." Potentials as low as 50 volts
may cause death under adverse conditions.
4-35
|